Features & Benefits
- AC/DC Measurement Capabilities
- DC – 100 MHz, Current Probe Amplifier (TCPA300) Uses:
- DC – 100 MHz, 30 A DC (TCP312)
- DC – 50 MHz, 50 A DC
(TCP305)
- DC – 15 MHz, 150 A DC (TCP303)
- DC
– 50 MHz, Current Probe Amplifier (TCPA400) Uses:
- DC
– 2 MHz, 750*1 A DC (TCP404XL) (500 A DC Continuous)
- Automatic Scaling and Units*2 – Oscilloscope
On-Screen Readout of Magnitude and Amps Reduces Measurement Errors
with No More Hand Calculations
- AC/DC Input Coupling
- Low Insertion Impedance Reduces Device Under Test Loading
- Split-Core Construction Allows Easy Circuit Connection
- Status
Indicators Provide Visual Operating Status and Notification of Potential
Error Conditions – Degauss, Probe Open, Overload, Not Terminated into
50 Ohm, Noncompatible Probe Type
- Lower DC Drift and Noise
Allows Improved Low-level Current Measurements
- Certified
for use in U.S., Canada, and Europe. Complies with applicable IEC
standards.
Applications
- Development and Analysis
Solutions for Designers, Installers, and Service Personnel in Telecomm,
Data Comm, Computer, and Semiconductor Power Electronics Environments
For:
- Power Supplies (Switching and Linear)
- Semiconductor Devices (SCRs, IGBTs, MOSFETs, CMOS, BJTs)
- Power Inverters/Converters
- Electronic Ballasts
- Industrial/Consumer Electronics
- Mobile Communications (Phone,
Satellite, Relay Stations)
- Motor Drives
- Transportation
Systems (Electronic Vehicles, Electric Trains, Locomotives, Avionics)
Increased
performance and simplicity
The TCP300 and TCP400 series AC/DC
Current Measurement family is a highly advanced current measurement
system for today's current measurement needs. The split-core probes
incorporate both transformer and Hall-effect technology to provide
broad bandwidth measurement capabilities from DC up to 100 MHz at
current levels as low as 1 milliamp to thousands of amps (when used
with CT4 current transformer). When connected to Tektronix Oscilloscopes
with TEKPROBE Level II, TekConnect (w/ TCA-BNC) or TekVPI (w/ TPA-BNC)
interfaces, current measurements and calculations are simple and easy.
Additional measurement power is available with add-on software
such as the TDSPWR2 power measurements package. With all this measurement
power, current measurements have never been easier.
*1 Derated with Duty Cycle
*2 Requires a TDS TEKPROBE
Oscilloscope or a TekConnect Oscilloscope with TCA-BNC
Meets
today's AC/DC current measurement applications
The TCPA300
amplifier, when used with TCP312, TCP305, or TCP303 probes, provide
a wide range of current measurement capability and spans the gap between
low-level milliamp measurements to very high current levels. These
three probes provide current measurement capabilities of 30 A, 50 A,
and 150 A DC continuous. For even higher current levels, the TCPA400
amplifier with the TCP404XL current probe measures 500 A DC continuous
and 750 A DC continuous, derated with duty cycle.
Higher frequency
performance is available with the TCP312 w/TCPA300 providing ≥100-MHz
bandwidth and a maximum current of 30 A DC.
Measurement errors
and manual calculations are now a thing of the past
With this
new series of current measurement tools, automatic control and on-screen
scaling and units is provided for users of Tektronix TDS3000, TDS500,
TDS600, TDS700, TDS5000, TDS6000, and TDS7000B series oscilloscope
systems (the DPO3000, DPO4000, and DPO7000 series oscilloscopes, the
TPA-BNC adapter is required).
The TCP300/TCP400 Current Measurement
Systems seamlessly integrate with your TDS series oscilloscope and
the TDSPWR2 software package to easily make those time-consuming power
measurements and calculations for you.
Even non-TEKPROBE systems
can use the TCPA 300/400 series to make proper current measurements
by simply multiplying the measured output voltage on the oscilloscope
by the TCPA 300/400 series range setting.
Ordering Information
TCP312
Probe;
AC/DC Current, DC to 100 MHz; 30 A DC (Requires TCPA300 Amplifier)
TCP305
Probe; AC/DC Current, DC to 50 MHz; 50 A DC (Requires
TCPA300 Amplifier)
TCP303
Probe; AC/DC Current, DC
to 15 MHz; 150 A DC (Requires TCPA300 Amplifier)
TCP404XL
Probe; AC/DC Current, DC to 2 MHz; 500 A DC (750 A DC Derated
With Duty Cycle) (Requires TCPA400 Amplifier)
All TCP300/TCP400
Current Probes Include: AC/DC Current Probe; Instruction Sheet;
Probe Cover; Certificate of Traceable Calibration
TCPA300
Amplifier; AC/DC Current Probe, DC to 100 MHz, (Requires TCP305
or TCP312 or TCP303 Probes)
TCPA400
Amplifier; AC/DC
Current Probe, DC to 50 MHz, (Requires TCP404XL Probe)
All TCPA300/TCPA400 Current Probe Amplifiers Include: AC/DC Current
Probe Amplifier; Instruction/Service Manual; TEKPROBE Interface Cable;
Male to Male BNC cable (50 Ω); 50 Ω feed-through termination; Certificate
of Traceable Calibration
Options
TCPA300/TCPA400
Power Plug Options
Opt. A1 - Euro
Plug, 220 V, 50 Hz
Opt. A2 - UK Plug, 240 V, 50 Hz
Opt. A3 - Australian Plug, 240 V, 50 Hz
Opt.
A5 - Swiss Plug, 220 V, 50 Hz
Opt. A6 - Japanese
Plug, 100 V, 110/120 Volt, 60 Hz
Opt. AC - China Plug,
50 Hz
Opt. A99 - No Power Cord
Language
Options
L5 - Japanese Manual
All TCP300/TCPA300/TCP400/TCPA400
Series
Service Options
Opt. C3 - Calibration Service 3 Years
Opt. C5 - Calibration
Service 5 Years
Opt. D1 - Calibration Data Report
Opt. D3 - Calibration Data Report 3 Years (with Option
C3)
Opt. D5 - Calibration Data Report 5 Years (with
Option C5)
Opt. R3 - Repair Service 3 Years
Opt. R5 - Repair Service 5 Years
Protective covers
RECOMMENDED ACCESSORIES
016-1923-00
- Cover, Small Probe Protective; (for TCP305, TCP312, A6302, A6302XL,
A6312, TCP202)
016-1924-00 - Cover, Large Probe Protective;
(for TCP303, TCP404XL, A6303, A6303XL, A6304XL)
016-1922-00
- Case, Transit; Current Measurement Systems
011-0049-02
- 50 Ω Feed Through Termination
012-0117-00 - 50 Ω
BNC To BNC Coaxial Cable
012-1605-00 - TEKPROBE Interface
Cable, TCPA300 or TCPA400 Amplifier to TDS series oscilloscopes
015-0601-50 - Current Loop, 1 Turn, 50 Ω, BNC Connector
(for TCP305, TCP312, A6302, A6302XL A6312, TCP202, TCP303, A6303,
A6303XL)
174-4765-00 - TCPA300/TCPA400 Amplifier Calibration
Adapter
067-1478-00 - Power Measurements Deskew Fixture,
For TCP202, TCP305, TCP312, TCP303, A6302, A6312, A6303, Series Probes
CT4 - AC Current Transformer, 20 kA (for use with TCP305,
TCP312, TCP202, A6302, A6312)
TDSPWR2 - Power Measurement
and Analysis Software for TDS5000 and TDS7000 Series Oscilloscopes
To order when purchasing oscilloscope:
Order: TDS5052PW2,
TDS5054PW2, TDS7054PW2,TDS7104PW2.
To order as Upgrade: